Input Power [System (SPS); Expansion (XPS);
Remote (RPS); and 100 W amplifiers]
120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz
220-240 VAC Models
2 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Power Supply Output
Ratings for SPS, XPS,
and RPS (see data
sheet S4100-0031 for
more detail)
Total Power Supply
Output Rating
Including module currents and auxiliary power outputs; 9 A total for
“Special Application” appliances; 4 A total for “Regulated 24 DC” power
Output
switches to
battery
during AC
failure or
brownout
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
NACs Programmed for
Auxiliary Power
2 A maximum per NAC;
5 A maximum total
Rated 19.1 to 31.1 VDC
Battery Charger
Ratings for SPS and
RPS (sealed lead-acid
batteries)
Battery capacity range
UL listed for battery charging of 6.2 Ah up to 110 Ah (batteries larger than 50 Ah require
a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
Charger characteristics
and performance
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per
UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
Environmental
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Model Description
4100-6034 Door Tamper Switch with built-in addressable IDNet IAM, one per cabinet assembly if required
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-1290 24 Point I/O Module; I Slot (see data sheet S4100-0032 for details)
4100-1293 Panel Mount Thermal Printhead Printer, supplied with one roll of paper; requires 3 Slots; see S4100-0032 for details
4190-9803 Replacement Paper for 4100-1293 Printer, one roll
4100-6045 Coded Manual Station Decoder Module; 3 Slot module; 85 mA supervisory, 163 mA alarm; see S4100-0018 for details
4100-6048 VESDA Air Aspiration Interface; 1 Slot module; 132 mA supervisory or alarm, see S4100-0026 for details
Model* Description Model* Description Model* Description
4100-5005 8 Zone IDC, Class B 4100-3110 250 Point IDNet 2+2 Module 4100-3202 4 DPDT Relays w/feedback, 10 A
4100-5015 8 Zone IDC, Class A 4100-3102 127 Point MAPNET II Module 4100-3204 4 DPDT Relays w/feedback, 2 A
4100-3109 250 Point IDNet 2 Module 4100-3103 MAPNET II Quad Isolator 4100-3206 8 SPDT Relays, 3 A
* See data sheet S4100-0031 for details
Model Description
4100-1279 Single blank 2” display cover; order as required (8 fill a bay front); two max. in a row between LED/switch modules
4100-2210 Appliqué, Canadian French, 4100ES Fire Control
4100-2300 Expansion Bay Hardware, order for each expansion bay (unless included with selected option)
4100-0636 Box Interconnection Harness Kit; order one for each close-nippled cabinet
4100-0632 Terminal Block Module; 2, 16 position terminal blocks mounted on 4” x 5” single block size, for up to 12 AWG wire (3.31 mm
2
)
4100-5128 Battery Distribution Terminal Block; mounts to side of box; required for close-nippled cabinets that interconnect battery wiring
7 S4100-0036-15 10/2014
Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2
Expansion Bay Chassis
Block A
Block B
Block C
Block D
Block E
Block F
Block G
Block H
Size Definitions: Block = 4” W x 5” H (102 mm x 127 mm) card area
Slot = 2” W x 8” H (51 mm x 203 mm) motherboard with daughter card
General Specifications
Expansion Bay Module Loading Reference (exact locations are provided with shipped product)
Description Mounting
Terminal Block Module 4” x 5”, 1 block
Class B Physical Bridge 2”, 1 slot
Class X Physical Bridge 4”, 2 slots
System or Remote Power Supply
Blocks E, F, G & H
ONLY
Expansion Power Supply Blocks G & H ONLY
Audio Controller Modules Blocks A & B
Flex-35 Amplifiers, 2 max/bay*
Blocks E & F; C & D; or
A & B
Flex-50 Amplifiers, 2 max/bay* Blocks E & F or C & D
100 W Amplifiers, 1 max/bay Blocks E, F, G & H
100 W Backup Amplifiers, 1 max.
per bay with primary amplifier
Blocks A, B, C & D
Master Telephone Module Blocks A & B
Master Microphone Module (do
not mount next to telephone)
Two vertical Blocks,
any location
Telephone Module 1 Block
Operator LED/Switch Modules 1 Slot
* NOTE: When mounting dual Flex amplifiers on an
expansion bay, special mounting rules apply.
NDU with VCC – Additional Options
NDU or NDU with VCC Additional Options