Standard Module Details
Master Controller & Motherboard:
Mounts in Slot 4 of a two slot motherboard (Slots 3 and 4
of the Master Controller Bay) and provides one Class B or
Class A, RUI communications channel, available at Slot 4
RUI communications controls up to 31 devices per master
controller (on one or multiple RUI channels); devices
include: MINIPLEX transponders, 4603-9101 LCD
Annunciators, 4602-9101 Status Command Units (SCU),
4602-9102 Remote Command Units (RCU), 4602 Series
LED Annunciator Panels, 4100 Series 24 I/O and
LED/Switch modules
Up to four RUI channels are supported; use up to three
4100-1291 RUI expansion modules as required
A Network Interface Module is mounted in Slot 3
Optional Service Modem 4100-6030 mounts onto the
master controller board with its own on-board connections
System Power Supply:
Rating is 9 A total, including module currents; NACs are
disabled for NDU
For NDU with VCC, rated 9 A total with “Special
Application” appliances; 4 A total for “Regulated 24 DC”
appliance power; (see data sheet S4100-0031 for details)
Outputs are power-limited, except for the battery charger
System Power Supply (Continued):
Provides system power, battery charging, auxiliary power,
earth detection, and provisions for either an optional City
Connect Module or an optional Alarm Relay Module
Battery Charger is dual rate, temperature compensated,
and charges up to 50 Ah sealed lead-acid batteries
mounted in the battery compartment; also is UL listed
for charging up to 110 Ah batteries mounted in an
external cabinet (see data sheet S2081-0012 for details)
Battery and Charger Monitoring includes battery
charger status and low or depleted battery conditions;
status information provided to the master controller
includes analog values for: battery voltage, charger
voltage and current, actual system voltage and current,
and individual NAC currents (where applicable)
NDU, 2 A Auxiliary Power Output is for local power
requirements (SPS Aux relays are not used)
NDU w/VCC, 2 A Auxiliary Power Output is selectable
for detector reset, door holder, or coded output operation
Optional City Connect Module (4100-6031, with disc.
switches, or 4100-6032, without disc. switches) can be
selected for conventional dual circuit city connections
Optional Alarm Relay Module (4100-6033) provides
three Form C relays that are used for Alarm, Trouble,
and Supervisory, rated 2 A resistive @ 32 VDC
4 S4100-0036-15 10/2014
Model Description Size Supv. Alarm
4100-6056 Wired Network Media Card
Select per Network connection requirements, two media cards
are required per network interface; mounts on the supplied
Network Interface Module(s); Class B or Class X operation
N.A. 55 mA 55 mA
4100-6057 Fiber Optic Media Card N.A. 25 mA 25 mA
4100-6055
Network Access Dial-in Service Modem, mounts to supplied Network Interface Module,
requires telephone line connection
N.A. 60 mA 60 mA
4100-1291 Remote Unit Interface Module (RUI); up to three maximum per control panel 1 Slot 85 mA 85 mA
4100-6030
Service Port Modem for local panel access only, mounts to Master Controller Module,
requires telephone line connection, accesses same information as front panel port
N.A. 70 mA 70 mA
4100-6031 City Circuit, with disconnect switches
For use with SPS
only, not RPS
Select one per SPS
(mounts on
SPS/RPS)
N.A. 20 mA 36 mA
4100-6032 City Circuit, without disconnect switches N.A. 20 mA 36 mA
4100-6033 Alarm Relay, 3 Form C relays, 2 A @ 32 VDC (one per RPS) N.A. 15 mA 37 mA
4100-6038 Dual RS-232 Interface; 3 maximum; can mount in Slot 3 or Slot 2 of Master Controller 1 Slot 132 mA 132 mA
4100-6046 Dual Port RS-232 standard interface (4 x 5 module) 1 Block 60 mA 60 mA
4100-6052 DACT, Point or Event Reporting; includes 2, 14 ft (4.3 m) DACT cables 1 Slot 30 mA 40 mA
4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA
4100-6102 Physical Bridge, Class A, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA
4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules; 3 A @ 8 VDC maximum 1 Block included with loads
4100-9816 Master Clock Interface Module with one standard RS-232 port (see S4100-0033) 1 Slot 132 mA 132 mA
4100-6079 SafeLINC internet interface module 2 Slots 145 mA 145 mA
Network Display Unit, Non-
oice*
Model Model Type/Listing Description Supv. Alarm
4100-9141 120 VAC Input UL 4100ES NDU with Master Controller, LCD and operator interface,
Network Interface Module (select media card separately), 9 A system
power supply/battery charger, and external RUI communications interface
(power supply/battery charger is an SPS with its IDNet channel and NACs
disabled)
419 mA 476 mA
4100-9143 Canadian, English ULC
see below for
selected Network
Media Card current
4100-9144 Canadian, French ULC
4100-9241 220-240 VAC Input UL
Network Display Unit with Voice Command Center (VCC)*
Model Model Type/Listing Description Supv. Alarm
4100-9142 120 VAC Input UL 4100ES NDU with VCC includes the first bay equipment described for the
NDU (above) and a second bay assembly with separate: Master
Controller for voice functions, Network Interface (select media card
separately), and a standard SPS with 250 point IDNet channel; and 3, 3 A
Class A/B NACs capable of SmartSync two-wire operation
828 mA 907 mA
4100-9145 Canadian, English ULC
see below for
selected Network
Media Card current
4100-9146 Canadian, French ULC
4100-9242 220-240 VAC Input UL
* For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045.
NDU Equipment Selection
NDU, or NDU with VCC Communication Modules (with exceptions as noted)
Comentários a estes Manuais